- South Korea / 2004
BR10 Series Recloser
- ◾ Price: Negotiable
- ◾ MOQ: Negotiable
BR10 Series Recloser
- ◾ Price: Negotiable
- ◾ MOQ: Negotiable
-
Required Quantity
-
Brand name
-
Shipping / Lead TimeNegotiable / Negotiable
-
Keyword
-
Category
Specifications
| Size | - | Weight | - | Stock | - |
|---|---|---|---|---|---|
| Country of Origin | South Korea | ||||
| Production method | Negotiable | ||||
| HS Code | 853521 | ||||
Trade Terms
| Payment Terms | - | ||||
|---|---|---|---|---|---|
| Price(FOB) | Negotiable | MOQ | Negotiable | ||
| Transportation | - | ||||
| Lead time | Negotiable | Shipping time | Negotiable | ||
Company
-
Country / Year Established
-
Membership
- VIP
Business typeManufacturer
-
Verified Certificate
-
6
-
-
6
-
Main Export Markets
-
Indonesia
-
Product Description
- -The BR-10 series Recloser Control, which is connected to automatic circuit recloser, is installed on the medium voltage distribution network. The Recloser Control, through the built-in voltage and current sensors of the Recloser, performs monitoring, fault detection, and protection function on distribution networks. Furthermore, utilities, by using separate communication networks and automation system, can remotely monitor and control the equipment.
- -The Recloser is installed at substations or distribution networks, and if fault currents are detected on installation points, it will clear the fault by operating according to the TCC characteristics.
- -As the Recloser is equipment that directly breaks faults occurred on lines so that it prevents faults from spreading to source sides, it is a protection device that performs the most important role in protecting the distribution networks.
- -These are the most core equipment together with the LBS in improving supply reliability in the whole distribution network and building automation system.
- -The LBS or the sectionalizer performs fault detection or auto-sectionalizing function by detecting the operations of the Recloser
- -Automatic Circuit Recloser for overhead lines is divided into SF6 or solid insulated type depending on an insulation method.
- -The Recloser is equipped with voltage and current sensors to monitor the status of the distribution networks and perform protection operations. For voltage sensors, they are basically installed on each side.
- -The Recloser is structured to be operated by a driver with a single permanent magnetic actuator, and guarantees operation reliability as well as constant opening and closing time.
- -The vacuum interrupter and the insulator being used are highly reliable products that have been sufficiently field-tested for their performances.
- -For solid insulated recloser, Hydrophobic cycloaliphatic epoxy is used as an insulator.
- -All electronic components are included in the control cubicle for reliability and easy maintenance.
Ratings
| Ratings | 12kV | 24kV | 36kV |
|---|---|---|---|
| Applied Standard | ANSI/IEEE Std. C37.60, or IEC 62271-111 | ||
| Rated Voltage(kV) | 17.5 | 27 | 38 |
| Rated Current(A) | 630 / 800 | 630 | 630 / 800 |
| Rated Frequency(Hz) | 60/50 | 60/50 | 60/50 |
| Rated Short-Time Current(kA) | 16,1 / 1 or 3sec | 16,1 / 1 or 3sec | 16,1 / 1 or 3sec |
| Rated Making Current(kAp) | 40 | 40 | 40 |
| Rated Power-frequency withstand Voltage(kV) | 50 | 60 | 70 |
| Impulse withstand Voltage(kV) | 110 | 150 | 180 |
| Mechanical Endurance(times) | 10,000 | 10,000 | 10,000 |
| Insulating Medium | SF6 gas / Solid | ||
| Operating Mechanism | Manual and Permanent Magnetic Actuator | ||
| Bushing Material | Polymeric / Epoxy | ||